Sign In | Join Free | My himfr.com
himfr.com

Wuhan Huaying Electric Power Tech & Science Co., Ltd

Wuhan Huaying Electric Power Tech & Science Co., Ltd 20 YEARS experience in design and manufacture Hipot Test Set Export to 50 Countries Worldwide Professional Technical Support ISO/CE/CNAS/SGS

Active Member

8 Years

Home > CT PT Test Set >

Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss

    Buy cheap Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss from wholesalers
     
    Buy cheap Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss from wholesalers
    • Buy cheap Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss from wholesalers
    • Buy cheap Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss from wholesalers
    • Buy cheap Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss from wholesalers

    Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss

    Ask Lasest Price
    Brand Name : Huaying
    Model Number : HYVA-405
    Certification : ISO/CE
    Price : Negotiable
    Supply Ability : 10 units per week
    • Product Details
    • Company Profile

    Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss

    Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss


    Product name: CT PT Analyzer HYVA-405


    Reference Standard

    GB 1207-2006, GB 1208-2006 (IEC 60044-1), GB16847-1997 (IEC 60044-6) , IEEE C57.13-1993


    HYVA-405 is mainly used to detect on phase error, ratio error, burden and admittance test of CT&PT. In addition, it supports data save and site printing, this can not only omit a lot of troublesome work such as manual voltage regulating, manual record and curve tracing, but also dump testing data through USB interface with USB disk .


    Features

    ★ Wide range, it can do CT test from 50/5 zero-sequence CT to 35000/1 generator CT.
    ★ Simple operation, all parameters and projects of the transformer are tested with one click
    ★ Ultra-high measurement precision, Typical ratio measurement error is only 0.02%
    ★ With powerful data management function, single machine can store more than 5000 groups data.
    ★ Intelligent assessment, it makes conclusion automatically whether the transformer test is qualified.
    ★ Strong application software support, make word reports for test result in bulk
    ★ Complete transformer on-site calibration without standard transformer, strong current power source, and load-box


    Technical Parameters:

    1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
    2 Power supply: AC220V±10%, 50/60Hz±10%
    3 Voltage output: 0.1~180V (AC)
    4 Current output: 0.001~5A(RMS)
    5 Power output: 500VA
    6 Maximum knee voltage measurement: 45KV
    7 Current measurement:
    Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
    Error: <±0.1%+0.01%FS
    8 Voltage measurement:
    Range: 0~200V (automatically change range in 1V/10V/70V/200V)
    Error: < ±0.1%+0.01%FS
    9 Turns ratio measurement:
    Range:1~35000
    1~2000 error<0.05%
    2000~5000 error<0.1%
    5000~35000 error<0.2%
    10 Phase measurement: error: ±2min; resolution: 0.01min
    11 Winding resistance measurement:
    Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
    Error: < 0.2%RDG+0.02%FS
    Maximum resolution: 0.1mΩ
    12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
    13 CT Secondary burden:
    Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
    Error: <0.2%RDG+0.02%FS
    Maximum resolution: 0.001ohm
    14 PT Secondary burden:
    Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
    Error :<0.2%RDG+0.02%FS
    Maximum resolution: 0.1ohm
    15 PT ratio measurement:
    Range: 1~35000
    1~10000 error<0.1%
    10000~35000 error<0.2%
    16 PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
    17 PT phase angle measurement: maximum error < 3min
    18 Make evaluation for test results according to selected standards
    19 Make word report for test result
    20 Make word reports one time for multi-group test records on the PC
    21 Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
    22 Compare excitation curves with saved excitation curves in the same window
    23 Memory capacity: >1000 groups test results
    24 Working condition: temperature: -10℃~50℃; moist: ≤90%

    Quality Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Wuhan Huaying Electric Power Tech & Science Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)