Sign In | Join Free | My himfr.com
himfr.com

Wuhan Huaying Electric Power Tech & Science Co., Ltd

Wuhan Huaying Electric Power Tech & Science Co., Ltd 20 YEARS experience in design and manufacture Hipot Test Set Export to 50 Countries Worldwide Professional Technical Support ISO/CE/CNAS/SGS

Active Member

8 Years

Home > Primary Current Injection Test Set >

Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance

Wuhan Huaying Electric Power Tech & Science Co., Ltd
Contact Now
    Buy cheap Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance from wholesalers
     
    Buy cheap Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance from wholesalers
    • Buy cheap Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance from wholesalers

    Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance

    Ask Lasest Price
    Brand Name : Huaying
    Certification : ISO
    Model Number : Huaying Series
    Price : negotiable
    Delivery Time : 7 Working Days
    Payment Terms : T/T L/C
    Supply Ability : 200 sets per month
    • Product Details
    • Company Profile

    Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance

    Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance


    1. Product Name:

    Primary Current Injection Test System SLQ

    2. Equipment Description:

    ​SLQ primary injection test set is a high current generator instrument. It is applied in current transformer test , circuit breaker test and so on. Adjustable output current, smooth in current rise, large scope of load variation, easy and safe operation.

    3.Fuction and Aplication:

    The main applications and functions of SLQ are as follow:
    1) High current output injected to the main circuit of power line to simulate the fault current.
    And then check whether the protection system will be operated according to the design
    2) High current output injected to the primary of current transformer and then measure the inducted current from secondary by error measurement instrument to check the ratio error and phase displacement of CT
    3) High current output injected to the main circuit of circuit breaker to simulate the rated current in primary. And then check the stability of circuit breaker according to the temperature rise procedure.
    4) Considered as a AC high current source in power equipment or cable test


    4.Technical Parameters:


    Type

    Capacity

    (kva)

    Power supply

    Output

    Impedance voltage %

    Idle current %

    mode

    I

    (A)

    V

    (V)

    I

    (A)

    V

    (V)

    SLQ-5/500

    3

    13.6

    220

    500

    5

    >8

    >6

    single

    SLQ -5/1000

    5

    22.7

    220

    1000

    5

    >8

    >6

    single

    SLQ -10/2000

    10

    46

    220

    2000

    5

    >8

    >6

    Separated

    SLQ -12/4000

    12

    30

    400

    2000/4000

    6/3

    >8

    >6

    Separated

    SLQ -15/5000

    15

    37.5

    400

    2500/5000

    6/3

    >8

    >6

    Separated

    SLQ -150/25kA

    150

    375

    400

    25000

    6

    >8

    >6

    Separated


    Quality Relay Protection System Primary Current Injection Set 1 Year Free Lifelong Maintenance for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Wuhan Huaying Electric Power Tech & Science Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)